The City of Danville Electric Division is seeking a quotation for a three-phase 7.2 kv to 277/480v 2500 kva pad mount unit per specification E-87-10. The unit should be self-cooled, designed for outdoor conditions, and manufactured in North America. The quotation should include the unit price, extension, total, payment terms, freight terms, delivery promised, telephone, fax, quote valid until, and vendor quotation number. The successful bidder will be required to supply three copies of test results, including no-load losses, exciting current, induced-potential test, ratio tests, pressure leak test, polarity and phase relation tests, impedance and load-loss test results, and resistance measurements of all windings.
• The unit should be designed to meet the requirements of the City of Danville Electric Division.
• The unit should be manufactured in North America.
• The unit should be self-cooled and designed for outdoor conditions.
• The quotation should include all the necessary information, including unit price, extension, total, payment terms, freight terms, delivery promised, telephone, fax, quote valid until, and vendor quotation number.
• The successful bidder will be required to supply three copies of test results.